EasyManua.ls Logo

Siemens SIPROTEC 7SD610 - Page 100

Siemens SIPROTEC 7SD610
438 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2 Functions
100
7SD610 Manual
C53000-G1176-C145-4
Figure 2-38 Logic diagram of the I>> stage
1
) Output indications associated with the pickup signals are listed in Table 2-3
2
) Output indications associated with the trip signals are listed in Table 2-4
Definite time over-
current stage I>
The logic of the overcurrent stage I> is the same as that of the I>> stages. In all ref-
erences Iph>> must merely be replaced with Iph> or 3I0>> PICKUP with 3I0>. Pa-
rameter 2624 I> Telep/BI is default as NO. In all other respects Figure 2-38 ap-
plies.
Additional Stage
I>>>
The additional definite time or instantaneous overcurrent stage I>>> has an extra
enable input (Figure 2-39) It is therefore also suitable e.g. as a stub protection or as
an emergency stage if the remaining stages are used as backup stages. The enable
input „>I-STUB ENABLE“ can be assigned to the output signal „Emer. mode“
(either via binary outputs and inputs or via the user-definable logic CFC functions).
The stage is then automatically active when the differential protection is not effective,
e.g. due to a data disturbance.
www . ElectricalPartManuals . com

Table of Contents

Other manuals for Siemens SIPROTEC 7SD610

Related product manuals