2 Functions
110
7SD610 Manual
C53000-G1176-C145-4
Table 2-4 Trip signals of the single phases
1)
If tripping by the 3I0 measuring unit is performed simultaneously or after tripping by a phase
measuring unit and if single-pole tripping is effective, „O/C TRIP 1p.L1“, „O/C TRIP 1p.L2“ or
„O/C TRIP 1p.L3“ is signaled.
2)
If tripping is only performed by the 3I0 measuring unit but not by a phase measuring unit,
„O/C TRIP L123“ is signaled.
Internal indication Display Output indication No
I>> TRIP L1
I> TRIP L1
I>>> TRIP L1
1)
I> ger TRIP L1
Ip TRIP L1
Ip ger TRIP L1
2-38
2-39
2-40
2-41
2-42
„O/C TRIP 1p.L1“ or „O/C TRIP L123“
7212 or
7215
I>> TRIP L2
I> TRIP L2
I>>> TRIP L2
1)
I> ger TRIP L2
Ip TRIP L2
Ip ger TRIP L2
2-38
2-39
2-40
2-41
2-42
„O/C TRIP 1p.L2“ or „O/C TRIP L123“
7213 or
7215
I>> TRIP L3
I> TRIP L3
I>>> TRIP L3
1)
I> ger TRIP L3
Ip TRIP L3
Ip ger TRIP L3
2-38
2-39
2-40
2-41
2-42
„O/C TRIP 1p.L3“ or „O/C TRIP L123“
7214 or
7215
I>> TRIP E
I> TRIP E
I>>> TRIP E
2)
I> ger TRIP E
Ip TRIP E
Ip ger TRIP E
2-38
2-39
2-40
2-41
2-42
„O/C TRIP L123“ 7215
I>> TRIP L1
I>> TRIP L2
I>> TRIP L3
I>> TRIP E
2-38
2-38
2-38
2-38
„O/C TRIP I>>“ 7221
I> TRIP L1
I> TRIP L2
I> TRIP L3
I> TRIP E
„O/C TRIP I>“ 7222
I>>> TRIP L1
I>>> TRIP L2
I>>> TRIP L3
I>>> TRIP E
2-39
2-39
2-39
2-39
„I-STUB TRIP“ 7235
I> ger TRIP L1
I> ger AUS L2
I> ger AUS L3
I> ger AUS E
2-40
2-40
2-40
2-40
„O/C TRIP I>Dir.“ 7236
Ip TRIP L1
Ip TRIP L2
Ip TRIP L3
Ip TRIP E
2-41
2-41
2-41
2-41
„O/C TRIP Ip“ 7223
Ip ger TRIP L1
Ip ger TRIP L2
Ip ger TRIP L3
Ip ger TRIP E
2-42
2-42
2-42
2-42
„O/C TRIP IpDir.“ 7237
(General TRIP) „O/C TRIP“ 7211