Supervisory Functions
153
7SS52 V4 Manual
C53000-G1176-C182-3
Permanent monitoring of the program flow
by means of watchdog (BU, CU)
After three unsuccessful restart attempts the
protection is blocked.
Differential current supervision
• Bus zone-selective protection
| Σ I | >Id> SUPERV BZ (6308/CU)
for T >T-Idiff SUPERV (6307/CU)
• Check zone, all except bus coupler
| Σ I | >Id> SUPERV CZ (6309/CU)
for T >T-Idiff SUPERV (6307/CU)
Current transformer circuit faulty
Bus zone-selective blocking
if the parameter DIF SUP mode BZ (6310/
CU) is set to blocking, otherwise only alarm
"IdSup Lz-y $03" (FNo. 177.1321,
177.1322, 177.1323, 177.1326,
177.1327, 177.1328/CU)
Blocking if the parameter
DIF SUP mode CZ (6311/CU) is set to
blocking, otherwise only alarm
"Id-Sup CZ Lz" (FNo. 10411, 10412,
10413/CU)
Monitoring of isolator status
• Running position
Isolator OPEN/CLOSED = 0/0
for T >ISOL TIME (6301/CU)
• Auxiliary voltage supply failure
All isolator positions
of one bay = 0/0
• Implausible isolator status
Isolator OPEN/CLOSED = 1/1
Wire break or intermediate status
Alarm "FltR $01 $02"
(FNo. 176.1112, 176.1117, 176.1122,
176.1127, 176.1132/CU)
Feeder aux. voltage MCB tripped
Alarm "BayDC fail $00"
(FNo. 176.1134/CU)
Alarm "FltP $01 $02" (FNo. 176.1113,
176.1118, 176.1123, 176.1128,
176.1133/CU)
Cyclic check of
the
data transmission links (FO) between
central unit and bay unit
Blocking of the protection system and alarm
after two recognitions of a transmission error
"Fail Com.CU" (FNo. 7650/BU)
Monitoring of
">CBF Lx", ">CBF 3-pole"
for T > 15 s
">CBF Lx", ">CBF 3-pole" and
">CBF release", ">release 3-pole"
for T > T-BF 2chan (XX28/CU)
">CBF release", ">release 3-pole"
for T >T-BF rel sup (XX27/CU)
">B.U.CBF Lx"
, ">B.U.CBF 3-pole"
for T = B.U.CBF-T (3912/BU) + 5 s
(but min. 15 s)
Alarm and blocking of the binary
input of the affected feeder
"BF-BIErr $00 Lz" (FNo. 176.1091,
176.1092, 176.1093/CU) or
"BF-BIErr $00 3P" (FNo. 176.1094/CU);
Supervision picks up if a signal is present at
the BI BF-phase for the time T > 15s;
Supervision picks up if both BI BF-phase and
BI BF release do not arrive within the time win-
dow T = limit;
Alarm and blocking of CBF
"BFRlErr $01 1P" (FNo. 176.1101/CU)
or
"BFRlErr $00 3P" (FNo. 176.1102/CU)
Cyclic test with simulation of a fault current
and monitoring of the entire signal process-
ing from the digitized measured values to
the control currents of the trip relay coils
After three recognitions of an error blocking of
the protection and alarm.
"Flt aut $00" (FNr. 176.1190/CU) and
"Flt autotest M" (FNr. 10429/CU)
Zero current monitoring Monitoring is done phase-selectively and the
alarm "Block ZeroCross" (FNo. 10444/
CU) is generated.
Monitoring Possible cause and response
www . ElectricalPartManuals . com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 7SS522 V4.6 and is the answer not in the manual?

Siemens SIPROTEC 7SS522 V4.6 Specifications

General IconGeneral
BrandSiemens
ModelSIPROTEC 7SS522 V4.6
CategoryPower distribution unit
LanguageEnglish

Related product manuals