Functions
180
7SS52 V4 Manual
C53000-G1176-C182-3
5.12 PC Port of the Bay Unit
5.12.1 Functional Description
The device is equipped with an operating interface integrated in the front panel, the
so-called PC port. Communication through this port is subject to certain agreements
concerning the transmission formation and the transmission rate.
The data entered must match the connected device.
5.12.2 Setting Notes
FUNCT. TYP With the parameter FUNCT. TYPE (7208/BU) you set the compatible functions type
for the transmission of your device with IEC61870-5-103.
The function type 160 (definite time mode) must be selected for the bay units.
PC INTERF. The parameter PC INTERF. (7211/BU) is used to select the format for transmitting
data from the front port (PC port) to the device connected to it.
With setting DIGSI V3, the data are transmitted in a format which is used by DIGSI V3.
With setting ASCII, the data are transmitted in ASCII format.
PC BAUDRATE The parameter PC BAUDRATE (7215/BU) is used to select the rate at which data will
be transmitted from the front port (PC port) to the device connected to it.
With setting 1200, 2400, 4800, 9600 or 19200 BAUD, the data will be transmitted at the
selected rate.
PC PARITY The parameter PC PARITY (7216/BU) is used to select the parity for transmission of
data from the front port (PC port) to the device connected to it.
With setting DIGSI V3, the data are transmitted with a parity used by DIGSI V3.
With setting No parity, 2 stopbits, data are transmitted without parity and with
2 stop bits.
With setting No parity, 1 stopbit, data are transmitted without parity and with
one stop bit.
SYS SUPV.T Use parameter SYS SUPV.T (7233/BU) to set the supervision time of the device
system interface.
The time set must be longer than the auto polling by the control system.
www . ElectricalPartManuals . com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 7SS522 V4.6 and is the answer not in the manual?

Siemens SIPROTEC 7SS522 V4.6 Specifications

General IconGeneral
BrandSiemens
ModelSIPROTEC 7SS522 V4.6
CategoryPower distribution unit
LanguageEnglish

Related product manuals