User-Defined Annunciations
197
7SS52 V4 Manual
C53000-G1176-C182-3
5.17 User-Defined Annunciations
5.17.1 Functional Description
The bay unit possesses four user-defined annunciations “Annuciation1” .. 4 (FNo.
7696/BU, 7697/BU, 7698/BU, 7699/BU) that you can define yourself and
assign to signal relays, LEDs or command relays.
Each user-defined annunciation is allocated to a delay time. The delay times are set
with the parameters T-Annunc.1 to T-Annunc.4 (2801/BU, 2802/BU, 2803/
BU, 2804/BU). Each of these four delay times can be started by its own binary input
>Annunc. 1 .. 4 (FNo. 11, 12, 13, 14/BU). After the delay time has elapsed
and if the parameter "ANNUN1byCU" .. "ANNUN4byCU" (2811/BU, 2812/BU,
2813/BU, 2814/BU) is set to NO, the user-defined annunications "Annunc. 1" ..
4 (FNo. 7696/BU, 7697/BU, 7698/BU, 7699/BU) are issued.
Input Annunciation
Central Unit
In addition, the delayed binary input annunciation >Annunciation1 .. 4 (FNo. 11,
12, 13, 14/BU) are transferred to the central unit. The associated input
annunciation at the central unit is BU INx $00 (FNo. 176.1141/BU, FNo.
176.1143/BU, FNo. 176.1145/BU, FNo. 176.1147/BU)
Output
Annunciation
Central Unit
In the central unit you can send 4 output annunciations “OUT1 $00“ (FNo.
176.1142/BU, FNo. 176.1144/BU, FNo. 176.1146/BU, FNo. 176.1148/
BU) to each bay unit to generate the “Annunciation1” .. 4 (FNo. 7696/BU,
7697/BU, 7698/BU, 7699/BU) .
Simulation of
Binary Input
These annunciation can be used optionally to simulate a binary input annunciation
having the meaning specified by parameter ANN1Fct.No to ANN4Fct.No (2821/BU
.. 2824/BU).
Bay Unit
Annunciation to
Central Unit
Up
to four annunciations available in the bay unit can be transferred to the central unit.
For this, use parameters ANN1Inp.No to ANN4Inp.No (2831/BU, 2832/BU,
2833/BU, 2834/BU) to select the desired annunciation number. Therefore, it is
unnecessary to assign the annunciation to the output relay and read it back via binary
inputs as user-defined annunciation.
The following figure shows a simplified schematic.
www . ElectricalPartManuals . com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 7SS522 V4.6 and is the answer not in the manual?

Siemens SIPROTEC 7SS522 V4.6 Specifications

General IconGeneral
BrandSiemens
ModelSIPROTEC 7SS522 V4.6
CategoryPower distribution unit
LanguageEnglish

Related product manuals