Device
163
7SS52 V4 Manual
C53000-G1176-C182-3
5.7 Device
5.7.1 Mode of operation
This section summarizes those annunciations which are not associated with any pro-
tection function.
5.7.2 Setting notes
TO IV-Bit Use parameter TO IV-Bit T103 (5299A/CU) to set the time that may elapse at the
maximum until reception of the synchronization pulse with external synchronization.
5.7.3 Annunciations
Reset Device Annunciation: The device has performed a start-up.
Relevant information: On
Initial start Annunciation: The device has performed an initial restart. All buffers have been reset.
The parameter settings are unaffected.
(Information supplied with the Reset Device annunciation)
Relevant information: On
Resume Annunciation: The device has performed a restart. Only internal buffers have been re-
set. Operational event, fault events, fault records and the parameter settings are un-
affected.
(Information supplied with the Reset Device annunciation)
Relevant information: On
Device OK Annunciation: Device is operational and protecting.
With this annunciation, the readiness relay picks up, and the Error LED goes out.
Relevant information: On
Setting Calc. Annunciation: Setting calculation is running.
Relevant information: On, the function is occupied by the parameter setting process.
Relevant information: Off, the function has been released again.
Settings Check Annunciation: the device is checking the new parameters (on-line parameter setting).
Relevant information: On, check has begun.
Relevant information: Off, the test is completed, i.e. the device is either operative
again, or the new parameters have been saved in a non-volatile memory, or no set-
tings check is running.
Level-2 change This annunciation is output as “On” as soon as the parameter set loaded with DIGSI
has been changed by an on-line parameter setting and the device is operating with the
new parameters.
The annunciation is “Off” as long as the parameter set loaded with DIGSI is not
www . ElectricalPartManuals . com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 7SS522 V4.6 and is the answer not in the manual?

Siemens SIPROTEC 7SS522 V4.6 Specifications

General IconGeneral
BrandSiemens
ModelSIPROTEC 7SS522 V4.6
CategoryPower distribution unit
LanguageEnglish

Related product manuals