Installation and Commissioning
284
7SS52 V4 Manual
C53000-G1176-C182-3
7.4.3.2 Check Zone
To test the check zone, the check zone must be set more selective than the busbar-
selective protection so that the supervision of the check zone picks up earlier.
Example You want to test the supervision of the check zone with the parameters for the differ-
ential current threshold Id> SUPERV CZ (6309/CU) = 0,2 I/I
no
and the delay time
T-Idiff SUPERV (6307/CU) = 2,0 s. For the busbar-selective protection the param-
eter Id> SUPERV BZ (6308/CU) is assumed to be set to 0,8 I/I
no
.
Test setup
 Arrange the test setup as in Chapter 7.4.2, page 279.
Test steps Check of the pickup threshold and the delay time:
 Increase the current in feeder 1 slowly until the check zone supervision picks up.
The measured current must correspond to the set current
Id> SUPERV CZ (6309/CU).
 Carry out a time measuring as in Chapter 7.4.3.3, page 284
Checking the blocking:
 The reaction of the protection when the differential current supervision of the check
zone picks up can be set with the parameter DIF SUP mode CZ (6311/CU) to
blocking or to only indicate (without protective blocking).
 Connect the bays 1 and 2 to the same bus zone.
 Increase the current in feeder 1 slowly until the supervision of the check zone picks
up.
 Apply to feeder 2 a current 4 times as high as the rated current I
N
. If the parameter
is set DIF SUP mode CZ (6311/CU) to blocking, no TRIP commands follow.
7.4.3.3 Time Delay
Time measuring is possible with the standard test equipment for protection devices.
 To measure the delay time for the differential current supervision, apply to feeder 1
through the testing device twice the current set in the parameter differential current
threshold Id> SUPERV BZ (6308/CU).
 As soon as the differential current supervision picks up, the test current source is
switched off. The measured time corresponds to the set delay time in parameter T-
Idiff SUPERV (6307/CU).
www . ElectricalPartManuals . com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 7SS522 V4.6 and is the answer not in the manual?

Siemens SIPROTEC 7SS522 V4.6 Specifications

General IconGeneral
BrandSiemens
ModelSIPROTEC 7SS522 V4.6
CategoryPower distribution unit
LanguageEnglish

Related product manuals