Introduction
6
7SS52 V4 Manual
C53000-G1176-C182-3
Output of indications to
Control center
LEDs
Binary outputs of the central unit
Commissioning support by measuring and display functions, and output of indica-
tions to a control center as well as to LEDs and outputs of the central unit.
Busbar
protection
The digital busbar protection contains the following functions:
Evaluation of the differential current in conjunction with through-current stabilization
(Figure 1-2, page 7)
Trip decision based on 3 independent measurements. 2 measurements are based
on busbar configuration, and the third measurement considers all busbar sections
independent of the isolator replica (check zone).
Fast tripping (typical trip time 15 ms)
Busbar protection with up to 12 bus zones (BZ), 12 bus coupler (auxiliary bus) sec-
tions (AB) and up to 48 bay units
Protection of systems with up to quintuple busbars (including transfer busbars)
Stabilization against spurious tripping in case of external faults and CT saturation
Zone-selective and phase-selective blocking of the busbar protection by the differ-
ential current monitor
Selective blocking of the bus section in case of
Isolator faults
Bay faults (bay unit, FO cable)
Measured value error
Response of the zero crossing supervision
Characteristics for check zone and bus-selective zones can be set independently
from each other
Normal pick-up characteristic (Figure 1-2, page 7)
Earth fault characteristic (Figure 1-3, page 7)
Matching to different CT ratios without interposing matching transformers
Selective clearance of short-circuits even on the bypass bus with signal transmis-
sion to the remote end
Detection and disconnection of short-circuits in the coupler bay between current
transformers and circuit-breaker based on current measurement and selective un-
balance
Detection and disconnection of short-circuits between current transformers and cir-
cuit-breaker of a line by end fault protection