Controlling Device Functions
227
7SS52 V4 Manual
C53000-G1176-C182-3
Blocking the TRIP
command -
busbar-selectively
The busbar-selective blocking of the TRIP command can be done at the central unit
for the connected bay units as well as at the bay units directly via DIGSI, binary input
or local operation
Blocking via the central unit is done with “$03 BlkTrip” (FNo. 177.1337/CU) or
a binary input “>Blk Trip $03” (FNo. 177.1336/CU) and is indicated by the
annunciation "$03 BlkdTrip" (FNo. 177.1338/CU) or "TRIP BZ blkd G" (FNo.
10497/CU). The annunciation "IsoProhib/Maint" (FNo. 10471/CU) is output.
The blocking via the bay unit is done via “>Blk.BB TRIP” (FNo. 7629/BU) or
BLOCKAGE ON?” (FNo. 4201/BU) is indicated by the annunciation "BB TRIP
block" (FNo. 7657/BU).
The system will always be reset when the blocking is deactivated, e.g. at the bay unit
with “BLOCKAGE OFF?” (FNo. 4202/BU), in order to completely terminate the
processes triggered by tests and checks (e.g. CBF).
In the case of a restart or a power failure the taggingBlocking BF” is retained. The
tagging is erased in the case of an initial start.
The annunciation "IsoProhib G" (FNo. 10471/CU) is output.
www . ElectricalPartManuals . com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 7SS522 V4.6 and is the answer not in the manual?

Siemens SIPROTEC 7SS522 V4.6 Specifications

General IconGeneral
BrandSiemens
ModelSIPROTEC 7SS522 V4.6
CategoryPower distribution unit
LanguageEnglish

Related product manuals