EasyManuals Logo

Siemens SIPROTEC 7SS522 V4.6 User Manual

Siemens SIPROTEC 7SS522 V4.6
440 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #296 background imageLoading...
Page #296 background image
Installation and Commissioning
280
7SS52 V4 Manual
C53000-G1176-C182-3
Figure 7-11 Test setup for the trip characteristic of the busbar-selective measuring system
Test steps  To prevent that the differential current supervision from blocking the protection dur-
ing the test switch it off with the parameter DIFF SUPERV (6306/CU).
 Set the differential current threshold and the stabilization factor for the busbar-se-
lective protection and the check zone as desired.
 Set the parameters I>TRIP (XX13/CU) for the overcurrent thresholds for the affect-
ed bays to 0.
 The test currents I
1
and I
2
must have a phase displacement of 180°. To find out the
phase angle, check the feeders 1 and 2 each with the same current (0.5 I
N
).
 If the connection is correct the differential current must be nearly zero and the sta-
bilization current must be the double of the supply current.
 If the differential current in not zero, check the connection. If that is correct reverse
the polarity in a feeder.
 If the current I
2
is zero, then increase the current I
1
for so long until a TRIP com-
mand is output. The current in the feeder must correspond to the differential current
threshold set in the parameter Id> BZ (6102/CU).
 Apply a constant current I
1
which is smaller than the set differential current thresh-
old to the feeder 1 from the test setup
 Increase the current I
2
in feeder 2 slowly until the protection trips.
 The following fomulas are valid:
Differential current I
d
= | I
1
+ I
2
|
Stabilizing current I
s
= | I
1
| + | I
2
|
Stabilizing factor k = I
d
/ I
s
= | I
1
+ I
2
| / (| I
1
| + | I
2
|)
1 For testing the diff-current limit for supervisory function (refer to Chapter 7.3.3, page 268)
Note
The percentages of the differential and stabilization currents refer to Normalized Cur-
rent (Chapter 4.3.7, page 60). The percentages of the feeders refer to the transformer-
rated value of the particular feeder. If the same percentages are displayed this does
not mean necessarily that the same current is flowing in the concerned feeders.
www . ElectricalPartManuals . com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 7SS522 V4.6 and is the answer not in the manual?

Siemens SIPROTEC 7SS522 V4.6 Specifications

General IconGeneral
BrandSiemens
ModelSIPROTEC 7SS522 V4.6
CategoryPower distribution unit
LanguageEnglish

Related product manuals