List of information - Central Unit
379
7SS52 V4 Manual
C53000-G1176-C182-3
10490 >Blocking back-up breaker
fail.prot. BU (>Block BF of BU)
BF-Protection SP on
off
* * LED BI BO 194 167 1 Yes
10491 Blocking back-up breaker
fail.prot. BU (Block BF of BU)
BF-Protection IntSP on
off
* * LED BO 194 168 1 Yes
10492 Back-up breaker fail.prot. of BU
blocked (Blkd BF of BU)
BF-Protection OUT on
off
* * LED BO 194 169 1 Yes
10493 >Blocking O/C protection of BU
(>Block O/C BU)
Protec. general SP on
off
* * LED BI BO 194 195 1 Yes
10494 Blocking O/C protection of BU
(Block O/C BU)
Protec. general IntSP on
off
* * LED BO 194 196 1 Yes
10495 O/C protection of BU blocked
(Blkd O/C BU)
Protec. general OUT on
off
* * LED BO 194 197 1 Yes
10496 BF protection BZ blocked (group
alarm) (BF BZ blkd G)
BF-Protection OUT on
off
**LEDBO
10497 Trip command BZ blocked (group
alarm) (TRIP BZ blkd G)
BB Protection OUT on
off
**LEDBO
30053 Fault recording is running (Fault
rec. run.)
Osc. Fault Rec. OUT * * * LED BO
009.0100 Failure EN100 Modul (Failure
Modul)
EN100-Modul 1 IntSP on
off
**LEDBO
009.0101 Failure EN100 Link Channel 1
(Ch1) (Fail Ch1)
EN100-Modul 1 IntSP on
off
**LEDBO
009.0102 Failure EN100 Link Channel 2
(Ch2) (Fail Ch2)
EN100-Modul 1 IntSP on
off
**LEDBO
176.1061 $00 out of service (OutOfServ
$00)
BU@ OUT on
off
* * LED BO 195 6 1 Yes
176.1062 $00 isolator maintenance (Maint-
en. $00)
BU@ OUT on
off
* * LED BO 195 3 1 Yes
176.1063 $00 failure (Failure $00) BU@ OUT on
off
* * LED BO 195 8 1 Yes
176.1071 Trip repeat $00 phase L1
(TripRep$00 L1)
BU@ OUT * on * LED BO 195 10 2 Yes
176.1072 Trip repeat $00 phase L2
(TripRep$00 L2)
BU@ OUT * on * LED BO 195 11 2 Yes
176.1073 Trip repeat $00 phase L3
(TripRep$00 L3)
BU@ OUT * on * LED BO 195 12 2 Yes
176.1081 No release of TRIP command
$00 (noTripRel $00)
BU@ OUT * on * LED BO 195 15 2 Yes
176.1082 Breaker fail/Transfer trip $00
(TrnsfTrip $00)
BU@ OUT * on * LED BO 195 16 2 Yes
176.1091 Timing error BF input $00 L1 (BF-
BIErr$00 L1)
BU@ OUT on
off
* * LED BO 195 18 1 Yes
176.1092 Timing error BF input $00 L2 (BF-
BIErr$00 L2)
BU@ OUT on
off
* * LED BO 195 19 1 Yes
176.1093 Timing error BF input $00 L3 (BF-
BIErr$00 L3)
BU@ OUT on
off
* * LED BO 195 20 1 Yes
176.1094 Timing error BF input $00 3pole
(BFB
IErr$00 3P)
BU@ OUT on
off
* * LED BO 195 21 1 Yes
176.1101 Timing error BF release $00 1P
(BFRlErr$00 1P)
BU@ OUT on
off
* * LED BO 195 23 1 Yes
176.1102 Timing error BF release $00 3P
(BFRlErr$00 3P)
BU@ OUT on
off
* * LED BO 195 24 1 Yes
176.1104 Timing error BF pulse $00 (BF-
PulsErr $00)
BU@ OUT on
off
* * LED BO 195 17 1 Yes
176.1110 $01 Isolator $02 ($01 $02)
1)
BU@ DP * * * LED BO 195 25 1 Yes
FNo. Description Function Type
ofIn-
for-
matio
n
Log-Buffer Configurable in Matrix IEC 60870-5-103
Event Log On/Off
Trip (Fault) Log On/Off
Ground Fault Log On/Off
Marked in Oscill. Record
LED
Binary Input
Function Key
Binary Output
Chatter Blocking
Type
Information No.
Data Unit
General Interrogation