7.9 High Feature 3RW5 HMI
SIRIUS 3RW52 Soft Starter
Manual, 01/2019, A5E35630451002A/RS-AD/004
117
7.9.4 Monitoring
7.9.4.1 Monitoring the measured values of the 3RW52 soft starter with the High Feature 3RW5
HMI
Requirements
You are in menu "Monitoring > Measured Values".
Procedure
Select a measuring value.
The menus "Phase Currents [%]" and "Phase Currents (rms)" contain further menu items,
which you can switch to with "OK".
Measured value
Setting
range
Explanation
Phase currents [%]
IL1
IL2
IL3
Average
The phase currents are displayed as a percentage. You can monitor
each phase (L1/L2/L3) individually, or the average of all 3 phases.
Phase currents (r.m.s.) [A]
The phase currents are displayed in amperes. You can monitor each
phase (L1/L2/L3) individually, or the average of all 3 phases.
Motor temperature rise [%] Current value of motor temperature rise in %. This value shows the
relative temperature rise of the motor.
Remaining motor cooling time [s] Remaining recovery time (minimum cooling time of motor) still to be
observed following activation of motor overload protection until the
3RW52 soft starter is once again ready for operation.
Remaining contact block cooling time [s] The remaining cooling time of the contact block is dependent on the
thermal capacity of the power unit and the ambient conditions
(temperature, air circulation, installation location etc.)
Contact block heating [°C] The currently calculated contact block temperature rise is
continuously compared with the previously stored contact block
temperature rise.