Messages and diagnostics
8.4 Faults and remedial actions of the 3RW52 soft starter
SIRIUS 3RW52 Soft Starter
134 Manual, 01/2019, A5E35630451002A/RS-AD/004
8.4 Faults and remedial actions of the 3RW52 soft starter
Error
No.
1)
Fault
Cause
Remedy
Manual
RESET
Remote
RESET
Auto RESET
303 Bus fault -
Acknowledgment
via Auto RESET
- - x
308 Switching
element defective
-
Check switching
elements L1, L2,
and L3.
Replace the
defective devices.
- - -
309 Switching
element overload
Switching element
(switching contact,
power semiconductor)
too hot.
Check the ambient
conditions linked to
cooling. You might
have to take
derating into
consideration.
Check the number
of switching
operations.
Acknowledgment
after cooling down
x x -
317 Electronics
supply voltage
too low
The supply voltage is
below the permissible
value.
Check the power
supply (load
dimensioning,
voltage range).
- - x
319 No supply
voltage
The power switch
is open or the
power supply is not
correctly
connected.
No current
Inspect the cables
and the cable
connections and
replace any faulty
components.
x x -
324 Temperature
sensor overload
The temperature of the
motor is too high.
Check the motor
and the application
that is driven by the
motor.
After tripping, you
cannot switch on
the motor again until
the temperature has
reached the
switching point of
the temperature
sensor.
x
2)
x
2)
x
2)