EasyManua.ls Logo

Siemens SIRIUS 3RW52 - Page 135

Siemens SIRIUS 3RW52
198 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Messages and diagnostics
8.4 Faults and remedial actions of the 3RW52 soft starter
SIRIUS 3RW52 Soft Starter
Manual, 01/2019, A5E35630451002A/RS-AD/004
135
Error
No.
1)
Fault
Cause
Remedy
Manual
RESET
Remote
RESET
Auto RESET
325 Temperature
sensor wire break
A wire has broken in
the sensor cable of the
temperature sensor.
Check the sensor
cable and the
temperature sensor.
x
2)
x
2)
x
2)
326 Temperature
sensor short
circuit
A short circuit has
occurred in the
temperature sensor
cable.
Check the sensor
cable and the
temperature sensor.
x
2)
x
2)
x
2)
327 Therm. motor
model overload
The motor feeder
has been
overloaded.
The motor
temperature rise
has exceeded a
limit.
Please check the
motor and the
applications that are
being driven by the
motor.
After tripping, you
can switch on the
motor again after
the cooling time has
expired or after
clearing the thermal
memory of the
motor.
x
2)
x
2)
x
2)
328 Motor overload
tripping
The motor feeder
has been
overloaded
The temperature
rise of the motor
has exceeded a
limit value.
Please check the
motor and the
applications that are
being driven by the
motor.
After tripping, you
can switch on the
motor again after
the cooling time has
expired or after
clearing the thermal
memory of the
motor.
x
2)
x
2)
x
2)
378 Installed firmware
is invalid /
inconsistent
The firmware is
incomplete and / or the
firmware expansions
are incomplete or
incompatible.
Execute a complete
firmware update.
Check any
occurring error
messages.
Check to see
whether the
firmware update has
been interrupted.
- - x

Table of Contents

Other manuals for Siemens SIRIUS 3RW52

Related product manuals