Maintenance and servicing
9.2 User test
SIRIUS 3RW52 Soft Starter
146 Manual, 01/2019, A5E35630451002A/RS-AD/004
9.2 User test
Requirements
3RW52 soft starter is in a fault-free condition.
Procedure
Depending on how long the RESET / TEST keys are held pressed, the following tests are
performed in the specified sequence. Thus, if the key is held pressed for longer than 5 s, all
3 tests are performed:
Operating time
Explanation
0.15 s ... 2 s
LED test
All 6 LEDs are activated.
2 s ... 5 s
Current detection test
Current measuring is tested in all 3 phases.
The thermistor motor protection can be optionally tested for short
circuits and overload.
> 5 s
Motor overload protection test
The entire control circuit is tested, including the contact blocks and the
error signaling output.
If the device responds as intended, tripping on overload occurs. This
can be reset immediately without a cooling time by pressing the
TEST / RESET key again.
You can also start the user test via the "Diagnosis > Self-test" menu of the 3RW5 HMI High
Feature. Here the user test is run through completely.
Note
To avoid faults, perform the tests with the motor switched off.
If the 3RW52
soft starter does not respond as shown in the tables during the function test,
check the conn
ections and the supply to the 3RW52 soft starter. If the fault persists even
though the connections are correct, the device must be replaced.