EasyManua.ls Logo

Siemens SIRIUS 3RW52 - Page 147

Siemens SIRIUS 3RW52
198 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Maintenance and servicing
9.2 User test
SIRIUS 3RW52 Soft Starter
Manual, 01/2019, A5E35630451002A/RS-AD/004
147
LED test
Display of test result
LED
pass
fail
"RN"
Lights up green
Off
"ER"
Lights up red
Off
"MT"
Lights up yellow
Off
"STATE / OVERLOAD"
Lights up yellow
Off
"RESET MODE"
Lights up green
Off
"Soft Torque"
Lights up green
Off
Current detection test
Display of test result
LED
pass
fail
"STATE / OVERLOAD"
Flickers red
Off
In case of error: System LEDs (RN,
ER, MT) flashing.
Device fault, replace device.