Parameter assignment
5.2 Overview of parameters
SIRIUS 3RW52 Soft Starter
80 Manual, 01/2019, A5E35630451002A/RS-AD/004
5.2 Overview of parameters
Parameters
Symbol
Setting range
Factory setting
Trip class for motor
overload protection
10A, 10E, 20E, OFF 10A
Rated operational current I
e
of the motor
1)
1 ... 16
2)
16
Current limiting value as a
multiple of the set rated
operational current I
e
of the
motor
1.3 ... 7 x I
e
Max.
4 x I
e
Ramp-up time
0 ... 20 s
If parameter value "0" is set, the
motor is switched on with a
ramp-up time of approx. 100 ms.
10 s
Starting voltage
30 ... 100 % 30 %
Ramp-down time
0 ... 20 s 0 s
Soft Torque
Off (LED off)
On (LED on)
Off
RESET MODE
Manual RESET (LED off)
Remote RESET (LED flashes
green)
Auto RESET (LED lit green)
Manual
RESET
1)
The rated operational current I
e
of the motor may, according to the standard, deviate by 20% from
the rating plate specification of the manufacturer.
2)
For meaning of scale, refer to laser-cut table on front panel of device.