Parameter assignment
5.2 Overview of parameters
SIRIUS 3RW52 Soft Starter
80 Manual, 01/2019, A5E35630451002A/RS-AD/004
5.2 Overview of parameters
Trip class for motor
overload protection
10A, 10E, 20E, OFF 10A
Rated operational current I
e
of the motor
1)
1 ... 16
2)
16
Current limiting value as a
multiple of the set rated
operational current I
e
of the
motor
• 1.3 ... 7 x I
e
• Max.
4 x I
e
Ramp-up time
• 0 ... 20 s
• If parameter value "0" is set, the
motor is switched on with a
ramp-up time of approx. 100 ms.
10 s
Starting voltage
30 ... 100 % 30 %
Ramp-down time
0 ... 20 s 0 s
Soft Torque
• Off (LED off)
• On (LED on)
Off
RESET MODE
• Manual RESET (LED off)
• Remote RESET (LED flashes
green)
• Auto RESET (LED lit green)
Manual
RESET
The rated operational current I
e
of the motor may, according to the standard, deviate by 20% from
the rating plate specification of the manufacturer.
2)
For meaning of scale, refer to laser-cut table on front panel of device.