Messages and diagnostics
8.3 Warnings and remedial measures
SIRIUS 3RW52 Soft Starter
Manual, 01/2019, A5E35630451002A/RS-AD/004
133
8.3 Warnings and remedial measures
Warning
Cause
Remedy
Connection abort in manual
mode
Connection to a local control station (e.g.
device HMI) has been interrupted.
Check the connection between the HMI
and the device.
Check the connection between the PC and
the local device interface.
Contact block overload Contact block (switching contact, power
semiconductor) too hot
Check the ambient conditions linked to
cooling. You might have to take derating
into consideration.
Check the number of switching operations.
Therm. motor model
overload
The motor feeder has been overloaded.
The motor temperature rise has
exceeded a limit.
Please check the motor and the
applications that are being driven by the
motor.
After tripping, you can switch on the motor
again after the cooling time has expired or
after clearing the thermal memory of the
motor.
Internal fan fault
Internal fan is dirty (not rotating freely).
Connecting cable has fallen off or is
defective.
Internal fan faulty
Check the function of the fan.
Clean the fan.
Check the wiring.
Replace the fan.