Functions
7.9 High Feature 3RW5 HMI
SIRIUS 3RW52 Soft Starter
Manual, 01/2019, A5E35630451002A/RS-AD/004
119
7.9.5 Parameterizing analog output AQ via the High Feature 3RW5 HMI
You can re-parameterize the output of the analog output with the 3RW5 HMI High Feature.
The actual average phase current L1 - L3 of the motor is displayed in % at the evaluation
unit via the analog output. Depending on the respective connecting terminal being used, the
signal can be displayed either as current or voltage.
● Terminals: AQ- / AQ I+
Measuring range of current output: 4 - 20 mA
● Terminals: AQ- / AQ U+
Measuring range of voltage output: 0 - 10 V
Requirements
● Access protection to 3RW5 HMI High Feature is not active or has been reset
● Device version with analog output
● Evaluation unit is connected properly. (Page 176)
● You are in menu "Parameters > Soft Starter > Analog Output".
Procedure
Output signal type
• Deactivated
• 4 - 20 mA (factory setting)
• 0 ... 10 mA
Via the "Output signal type" parameter you can define
with what type of signal the analog value is to be
output.
Range start value
• 0 (factory setting)
With parameters "Range start value" and "Range end
value" you can define which value of the analog value
to be output corresponds to the lower output signal
value and which to the upper output signal value.
• Setting of the analog range, e.g. 4 mA = 0
• Setting of the analog range, e.g. 20 mA = 96
Range end value
• 96 (factory setting)
Corresponds to 300% of the
average phase current (%).
Factor for calculating the output measured value
Phase current average (%)