Mounting and dismantling
3.4 Installing / mounting / removing 3RW5 HMI
SIRIUS 3RW52 Soft Starter
46 Manual, 01/2019, A5E35630451002A/RS-AD/004
3.4.5 Installing the Standard 3RW5 HMI into the control cabinet door
Requirements
Note the mounting positions, minimum clearances and ambient conditions stated on the
data sheet.
3RW5 HMI Standard (accessories)
An HMI connecting cable (accessory) of suitable length
Cutout of suitable size in the control cabinet door
PZ2 screwdriver in installation with door mounting kit IP65
Device depth of the Standard 3RW5 HMI:
Total depth: 32 mm
Embedded depth: 29 mm
Permissible wall thickness of the cabinet door:
Without IP65 door mounting kit: 1.5 to 3.0 mm
With IP65 door mounting kit: 1.0 to 7.0 mm
Optional accessories:
IP65 door mounting kit
Procedure without door mounting kit IP65
Place the 3RW5 HMI Standard in the cutout of the control cabinet door . Ensure that the
3RW5 HMI Standard engages audibly in the 4 fixtures
.