EasyManua.ls Logo

Siemens SIRIUS 3RW52 - Suggested settings

Siemens SIRIUS 3RW52
198 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter assignment
5.3 Suggested settings
SIRIUS 3RW52 Soft Starter
Manual, 01/2019, A5E35630451002A/RS-AD/004
81
5.3 Suggested settings
Application
Starting voltage
[%]
Ramp-up time [s]
Current limiting
function
Ramp-down time
[s]
Conveyor belt
(full)
70 5 7 × I
e
10
Roller conveyor
(full)
60 5 7 × I
e
10
Compressor
(without pressure)
50 4 4 × I
e
Not relevant
Small fan
40
2
4 × I
e
Not relevant
Pump
1)
40
3
4 × I
e
10
Hydraulic pump
40
2
4 × I
e
Not relevant
Agitator
40
2
4 × I
e
Not relevant
Milling machine
40
4
4 × I
e
Not relevant
1)
It is recommended that the Soft Torque function is activated.

Table of Contents

Other manuals for Siemens SIRIUS 3RW52

Related product manuals