5.7 Parameterizing output 13 / 14 (output signal ON or RUN)
SIRIUS 3RW52 Soft Starter
86 Manual, 01/2019, A5E35630451002A/RS-AD/004
5.7 Parameterizing output 13 / 14 (output signal ON or RUN)
Application
One of these two states is output at output 13 / 14:
ON
RUN
State diagrams of the inputs and outputs (Page 61)
Use the output function ON, for instance, to implement latching if you selected pushbutton
control.
Use the Output function RUN in order, for instance, to control a line contactor connected
upstream.
Requirements
Control supply voltage is connected.
The 3RW52 soft starter does not signal any faults, the LED STATE / OVERLOAD is off.
Procedure
1. Activate the programming mode by holding the MODE key down for longer than 2 s until
the LED STATE / OVERLOAD flickers green.
Hold the MODE key down.
2. Simultaneously press the RESET / TEST key down for longer than 1 s until the LED
STATE / OVERLOAD on the device lights up red.
The set state of relay output ON / RUN is displayed on the Soft Torque LED:
LED Soft Torque
Signal set on output 13 / 14
Flashes green
ON (factory setting)
Flickers green
RUN
3. Release the MODE and RESET / TEST keys.
4. Switch to the other mode by pressing the MODE key briefly. The Soft Torque LED
switches between flickering green and flashing green.
You can switch between the modes at the output as often as you want.
5. Terminate programming mode by pressing the RESET / TEST key for longer than 1 s
until LED STATE / OVERLOAD no longer shines red.