Messages and diagnostics
8.4 Faults and remedial actions of the 3RW52 soft starter
SIRIUS 3RW52 Soft Starter
136 Manual, 01/2019, A5E35630451002A/RS-AD/004
Error
No.
1)
Fault
Cause
Remedy
Manual
RESET
Remote
RESET
Auto RESET
381 Device error Irrecoverable fault
detected following self-
diagnostics (self-test,
contactor contacts,
switching element,
etc.).
Replace the device.
Please contact
Technical Support
(Support Request
(Page 31)).
- - -
1408 Zero current after
ON command
No current flow is
detected in the motor
feeder after an ON
command. Possible
causes:
Main circuit is
interrupted (fuse,
motor starter
protector)
Motor contactor or
contactor control is
defective
No load
Acknowledgment
once the cause has
been rectified.
x x -
1409
Phase failure L1
The main energy
monitoring system has
detected a phase
failure.
Acknowledgment
once the cause has
been rectified.
x x -
1410
Phase failure L2
1411 Phase failure L3
1417 Bypass defective
Bypass defective
The error can also
be generated by
successive, brief
interruptions of the
control supply
voltage.
Check the bypasses
for L1, L2 and L3
and replace any that
are defective.
Please contact
Technical Support
(Support Request
(Page 31)).
- - -
1418 Bypass protective
trip
An excessively high
current has occurred
in bypass mode.
Check the motor.
Check the
dimensioning of the
soft starter.
Acknowledgment
after cooling down
x x -
1454 Incorrect module
slot or faulty
configuration
There is a difference
between a real slot
and a slot configured
in the
SIRIUS Soft Starter
ES (TIA Portal).
Ensure consistency
between plugged
and configured
module. A wiring
error may also exist
at the referenced
module.
After the cause is
eliminated, the error
self-acknowledges.
- - -