Fundamental Principles and System Description
Engineering Information
SINAMICS Engineering Manual – November 2015
Ó Siemens AG
43/528
Output
power
SINAMICS
S120 BLM
at 400 V
or 690 V
[ kW ]
Frame
size
[ - ]
Rated
input current
[ A ]
Maximum
short-circuit current
[ kA ]
Minimum
short-circuit
current
[ kA ]
Min. relative
short-circuit
power
RSC
min
[ - ]
Max. relative
short-circuit
voltage
v
k max
[ % ]
SINAMICS S120 BLM / 380 V – 480 V 3AC
200 FB 365 65
1
/ 50
2
4.4 12.1 8.3
250 FB 460 65
1
/ 50
2
5.2 11.3 8.9
360 FBL 610 65
1
/ 50
2
8.8 14.4 6.9
400 FB 710 65
1
/ 50
2
10.0 14.1 7.1
560 GB 1010 84
1
/ 84
3
12.4
1
/ 2.5
3
12.3
1
/ 2.5
3
8.1
1
/ ≈ 10
3
600 FBL 1000 84
1
/ 84
3
12.4
1
/ 2.5
3
12.4
1
/ 2.5
3
8.1
1
/ ≈ 10
3
710 GB 1265 170
1
/ 100
3
18.4
1
/ 3.2
3
14.5
1
/ 2.5
3
6.9
1
/ ≈ 10
3
830 GBL 1420 170
1
/ 100
3
20.0
1
/ 3.2
3
14.1
1
/ 2.3
3
7.1
1
/ ≈ 10
3
900 GD 1630 170
1
/ 100
3
18.6
1
/ 4.0
3
11.4
1
/ 2.5
3
8.8
1
/ ≈ 10
3
SINAMICS S120 BLM / 500 V – 690 V 3AC
250 FB 260 65
1
/ 65
2
3.0 11.5 8.7
355 FB 375 65
1
/ 65
2
4.4 11.7 8.5
355 FBL 340 65
1
/ 65
2
4.4 12.9 7.7
560 FB 575 65
1
/ 50
2
8.0 13.9 7.2
630 FBL 600 65
1
/ 50
2
7.2 12.0 8.3
900 GB 925 84
1
/ 84
3
10.4
1
/ 2.0
3
11.2
1
/ 2.2
3
8.9
1
/ ≈ 10
3
1100 GB 1180 170
1
/ 85
3
16.0
1
/ 2.5
3
13.6
1
/ 2.1
3
7.4
1
/ ≈ 10
3
1100 GBL 1070 170
1
/ 85
3
16.8
1
/ 2.5
3
15.7
1
/ 2.3
3
6.4
1
/ ≈ 10
3
1370 GBL 1350 170
1
/ 85
3
16.8
1
/ 3.2
3
12.4
1
/ 2.4
3
8.0
1
/ ≈ 10
3
1500 GD 1580 170
1
/ 85
3
18.6
1
/ 3.2
3
11.8
1
/ 2.0
3
8.5
1
/ ≈ 10
3
1) These values apply to BLMs in Chassis format and do not take in account line-side fuse switch disconnectors or circuit breakers
2) These values apply to BLMs in Cabinet Modules format with fuse switch disconnectors including 3NE1 fuses in the LCM
3) These values apply to BLMs in Cabinet Modules format with circuit breaker in the LCM
SINAMICS S120 BLM: Maximum and minimum line-side short-circuit currents
Output
power
SINAMICS
S120 SLM
at 400 V
or 690 V
[ kW ]
Frame
size
[ - ]
Rated
input current
[ A ]
Maximum
short-circuit current
[ kA ]
Minimum
short-circuit
current
[ kA ]
Min. relative
short-circuit
power
RSC
min
[ - ]
Max. relative
short-circuit
voltage
v
k max
[ % ]
SINAMICS S120 SLM / 380 V – 480 V 3AC
250 GX 463 65
1
/ 50
2
6.2 13.4 7.5
355 GX 614 65
1
/ 50
2
9.2 15.0 6.7
500 HX 883 84
1
/ 84
3
10.4
1
/ 2.0
3
11.8
1
/ 2.3
3
8.5
1
/ ≈ 10
3
630 JX 1093 84
1
/ 84
3
16.0
1
/ 2.5
3
14.6
1
/ 2.3
3
6.8
1
/ ≈ 10
3
800 JX 1430 170
1
/ 100
3
21.0
1
/ 3.2
3
14.7
1
/ 2.2
3
6.8
1
/ ≈ 10
3
SINAMICS S120 SLM / 500 V – 690 V 3AC
450 GX 463 65
1
/ 50
2
6.2 13.4 7.5
710 HX 757 84
1
/ 50
2
10.5 13.9 7.2
1000 JX 1009 170
1
/ 85
3
12.4
1
/ 2.5
3
12.3
1
/ 2.5
3
8.1
1
/ ≈ 10
3
1400 JX 1430 170
1
/ 85
3
21.0
1
/ 3.2
3
14.7
1
/ 2.2
3
6.8
1
/ ≈ 10
3
1) These values apply to SLMs in Chassis format and do not take in account line-side fuse switch disconnectors or circuit breakers
2) These values apply to SLMs in Cabinet Modules format with fuse switch disconnectors including 3NE1 fuses in the LCM
3) These values apply to SLMs in Cabinet Modules format with circuit breaker in the LCM