2-54
1010PFM-3GSection 2
Assigning Io Output Functions
The Io analog output is a loop-powered (or externally powered), isolated 4-20 mA DC signal that varies
linearly in relation to a selected data function.
To assign a function for the current output:
From [Analog Out Setup], press twice to access the [Io] option list.
Move the cursor to the desired data function by pressing
To store selection press
Assigning Vo Output Functions
The Vo analog output is a 0-10 VDC signal that varies linearly in relation to a selected function.
To assign a function to the voltage output:
To access the [Vo] option list press
Move the cursor to the desired data function by pressing
To store selection press
Assigning Pgen Output Functions
The Pgen analog output is a buffered TTL-compliant pulse rate signal. It varies linearly from 0-5000 Hz
in relation to a selected data function.
To assign a function to the Pgen output:
To access the [Pgen] option list press
Move the cursor to the desired data function by pressing
To store selection press
ENT
ENT
ENT
2.10.2 RELAY SETUP
Use this menu to assign a function to channel relays. The system offers 2 types of relay outputs, Alarm
Relay and Pulse Relay. Alarm Relay outputs operate in “fail-safe” mode. The relay(s) are energized
under normal conditions - an alarm condition causes the relay(s) to de-energize until alarm clears.
Pulse Relay output supports totalizer and batch relay functions. The output pulse width is approxi-
mately 200 ms. The 1010 family of portable instruments use soild state logic levels rather than relays
PULSE OUTPUT (Pgen Wiring)
Models 1010P & 1010DP
Installation Drawings 1010P-7 (Sht 2 of 2) and 1010DP-7 (Sht 2 of 2)
PIN# SIGNAL FUNCTION NOTES
10 PGEN1 FREQUENCY OUTPUT 1 Pulse Freq Output (0-5kHz) 5V TTL CMOS Logic. Use
11 PGEN2 FREQUENCY OUTPUT 2 any available signal gnd for return (Terminal 1, 17 or 26)
Models 1010WP & 1010WDP
Installation Drawings 1010WP-7 (Sht 2 of 2) and 1010WDP-7 (Sht 2 of 2)
PIN# SIGNAL FUNCTION NOTES
K PGEN1 FREQUENCY OUTPUT 1 Pulse Freq Output (0-5kHz) 5V TTL CMOS Logic. Use
L PGEN2 FREQUENCY OUTPUT 2 any available signal gnd for return (Terminal A, T or c)