12.For the lower range value 0 bar, check the zero point (4 mA).
If the differential pressure lines ⑤ have equally high condensate columns with the same
temperature, the measurement result is error-free. Otherwise, repeat the zero-point
adjustment.
13.Close the stabilizing valve ②.
14.
Fully open the differential pressure valves ③ and ④.
Cleaning process cable
1. To clean the line, briefly open the drain valves ⑦.
2. Close the drain valve ⑦ before vapor escapes.
Commissioning
8.5 Application examples
SITRANS P320/P420 with 4 to 20 mA/HART
100 Operating Instructions, 11/2019, A5E44852162-AC