Step response time T
63
(without electrical damping) - absolute pressure from gauge and differential pressure series
Gauge pressure series
All measuring cells Approx. 0.105 s
Differential pressure series
250 mbar/25 kPa/3.6 psi Approx. 0.195 s
1300 mbar a/130 kPa a/18.8 psi a
5 bar a/500 kPa a/72.5 psi a
30 bar a/3000 kPa a/435 psi a
100 bar a/10 MPa a/1450.3 psi a
Approx. 0.145 s
Effect of mounting position - absolute pressure from gauge and differential pressure series
In pressure per change of angle
For absolute
pressure (from the gauge pressure series): 0.05 mbar/0.005 kPa/
0.000725 psi per 10° incline
For absolute pressure (from the differential pressure series): 0.7 mbar/0.07 kPa/
0.001015 psi per 10° incline
(zero-point correction is possible using the zero point adjustment)
13.2.6 Absolute pressure with front-flush diaphragm
Conformity error at limit point setting, including hysteresis and repeatability
Measuring span ratio r (spread, Turn-Down) r = max. measuring span/set measuring span and nominal
measuring range
Linear characteristic curve r ≤ 10 10 < r ≤ 30
All measuring cells ≤ 0.2% ≤ 0.4%
Effect of ambient temperature
In percent per 28 °C (50 °F)
All measuring cells ≤ (0.16 • r + 0.24)
Long-term stability at ±30 °C (±54 °F)
All measuring cells In 5 years ≤ (0.25 • r)%
Step response time T
63
(without electrical damping)
Approx. 0.105 s
Technical data
13.2 Measuring accuracy of SITRANS P320
SITRANS P320/P420 with 4 to 20 mA/HART
212 Operating Instructions, 11/2019, A5E44852162-AC