Siemens SITRANS P - Display of Measured Values

Siemens SITRANS P
280 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
The bar display shows the following information:
The position of a measured value within the set measuring span (e.g. pressure).
The position of the temperature value within the sensor limits.
The scaling of the process values calculated from the pressure value (e.g. volume flow).
7.2.2.1 Display of measured values
The following measured values are always displayed:
Pressure (P1)
Sensor temperature (P2)
Electronics temperature (P3)
Percent of range (P9)
Loop current (PA)
Terminal voltage (PB)
The following values are calculated from the measured pressure value and are displayed
depending on your application:
Level (P4)
Volume (P5)
Volume flow (P6)
Mass flow (P7)
Customized characteristic curve (P8)
Measured val‐
ue ID
Name of measured value Meaning
P1 PRESSURE Pressure
PRESS GAUGE Gauge pressure
PRESS ABS Absolute pressure
P2 SENSOR TEMP Sensor temperature
P3 ELECTR TEMP Electronics temperature
P4 LEVEL Level
P5 VOLUME Volume
P6 VOLUME FLOW Volume flow
P7 MASS FLOW Mass flow
P8 USER DEFINED Customized characteristic curve
P9 % OF RANGE Percent of range
PA LOOP CURRENT Loop current
PB CURR VOLTAGE Terminal voltage
You use the "Start view" parameter [32] to select the measured value that is displayed as the
first measured value in the measurement view.
Start view [32] (Page
142)
Operating
7.2 Operating the device with display
SITRANS P320/P420 with 4 to 20 mA/HART
Operating Instructions, 11/2019, A5E44852162-AC 77