3.8 mA
22.8 mA20 mA
20.5 mA
4 mA3.55 mA
① Normal operation
② Lower fault current (factory setting)
③ Lower saturation limit (factory setting)
④ Upper saturation limit (factory setting)
⑤ Upper fault current (factory setting)
9.2.12 Upper saturation limit [14]
Sets the threshold for the upper saturation limit④.
Setting range: Between 20 mA and the upper fault current
Factory setting: 20.5 mA, or as specified in order
3.8 mA
22.8 mA20 mA
20.5 mA
4 mA3.55 mA
① Normal operation
② Lower fault current (factory setting)
③ Lower saturation limit (factory setting)
④ Upper saturation limit (factory setting)
⑤ Upper fault current (factory setting)
Parameter assignment
9.2 Parameter assignment over device with display
SITRANS P320/P420 with 4 to 20 mA/HART
126 Operating Instructions, 11/2019, A5E44852162-AC