5.4.1 Remote seal with capillary line
Notes
Do not
transport the measuring assembly (pressure transmitter, flange and capillary line) to
the capillary line.
Do not bend the capillary lines. Otherwise there may be a leakage risk and the set-up time
of the measuring system is increased.
A mechanical overload at the connection points between capillary line and remote seal or
between capillary line and pressure transmitter will lead to potential bending or breaking.
Wind capillary lines that are too long with a radius of at least 300 mm.
Fasten the capillary line such that there are no vibrations.
Permissible height differences:
In the case of remote seal measuring systems with silicon, glycerin or paraffin oil filling,
the height difference of H
1max.
= 7 m must not be exceeded.
When halocarbon oil is used as fill fluid, the maximum height difference may only be
H
1max.
= 4 m; see installation type A and installation type B.
If a negative overpressure is observed during measurements, reduce the permissible height
difference.
Installation type for gauge pressure and level measurements (open containers)
+
+
+
X
+
R
Installation type A: Pressure transmitter
above the measuring point
Start of scale value:
p
LRV
= ρ
FL
* g * H
U
- ρ
oil
* g * H
1
Full-scale value:
p
URV
= ρ
FL
* g * H
O
- ρ
oil
* g * H
1
Installing/mounting
5.4 Installation with remote seal
SITRANS P320/P420 with 4 to 20 mA/HART
56 Operating Instructions, 11/2019, A5E44852162-AC