Example
For the volume measurement, you set the following values, for example:
Damping value: 2.0 s
Lower range value: 0.0 mbar
Upper range value: 500.0 mbar
Application: Cylinder vessel (CYLIN)
Unit: m
3
Lower scaling point: 0.0 m
3
Upper scaling point: 10.0 m
3
9.2.4.5 Set application
Procedure
1.
Navigate to the parameter view.
Navigating in the views
(Page 76)
2. Select the "Application" parameter [05].
3. Select the parameter value.
Application [05] (Page 110)
9.2.5 Application point [06]
Sets the application point from which scaling occurs according to the square root. Before the
application point, the scaling occurs in a linear relationship with the differential pressure.
This parameter is only visible when you have selected the characteristic curve "Linear, square
root" (VSLIN or MSLIN) using the "Application" parameter.
Setting range: 5 to 15%
Factory setting: 10%
See also
Volume and mass flow measurements
(Page
115)
9.2.6 Zero point adjustment [07]
Introduction
A series of factors, such as installation, static pressure, temperature or long-term stability, can
cause zero-point errors.