To compensate the liquid column on the minus side, reset the zero point.
0D[LPXPOHYHO
8SSHUUDQJHYDOXH
/RZHUUDQJHYDOXH
&RQVWDQW
&RPSDULVRQ
OHYHO
/LTXLGILOOHG
QHJDWLYHSUHVVXUHOLQH
3UHVVXUHWUDQVPLWWHU
UHIHUHQFHOLQH
'
-
K
2
K
8
K
Y
Measurement assembly on a closed container (strong condensate
formation)
Formula:
Lower range value:
Δp
MA
= g · (h
U
· ρ - h
V
· ρ')
Upper range value:
Δp
MA
= g · (h
O
· ρ
- h
V
· ρ')
h
U
Lower filling level Δp
MA
Lower range value
h
O
Upper filling level Δp
ME
Upper range value
h
V
Gland distance ρ Density of the measured medium in
the container
p Pressure ρ ' Density of fluid in the negative pres‐
sure
line
corresponds to the prevailing
temperature there
g Acceleration due to gravity
The process connection on the negative side is a female thread
1
/
4
-18 NPT or an oval flange.
Lay the line for the negative pressure using a seamless steel tube 12 mm x 1.5 mm.
5.4 Installation with remote seal
Notes
Keep the measuring system in the factory packing until it is installed in order to protect it from
mechanical damage.
When removing from the factory packing and installing: ensure that damage to and
mechanical deformations in the membrane are prevented.
Never loosen the sealed filling screws on the remote seal and the measuring instrument.
Installing/mounting
5.4 Installation with remote seal
SITRANS P320/P420 with 4 to 20 mA/HART
54 Operating Instructions, 11/2019, A5E44852162-AC