4.4.2.7 Measuring cell for level



Inlet pressure P
+
Overload diaphragm
Seal diaphragm on the measuring cell Inlet pressure P
-
Pressure cap Filling liquid of the measuring cell
O-ring Capillary tube with the fill fluid of the mounting
flange
Differential pressure sensor Flange with a tube
Measuring cell body Seal diaphragm on the mounting flange
Figure 4-13 Function chart of the measuring cell for level
The inlet pressure (hydrostatic pressure)
works hydraulically on the measuring cell
through the seal diaphragm on the mounting flange
.
The differential pressure at the measuring cell is transmitted to the differential pressure
sensor through the seal diaphragms and the filling liquid .
When measuring limits are exceeded, the overload diaphragm is displaced until one of
the seal diaphragms or rests on the measuring cell body . The seal diaphragms
thus protect the differential pressure sensor from overload.
The seal diaphragm is displaced by the differential pressure. The displacement changes
the resistance of the four doped piezoresistors in the bridge circuit.
The change in the resistance causes a bridge output voltage proportional to the differential
pressure.
4.5 System configuration
Introduction
The pressure transmitter can be used in a number of system configurations:
As a stand-alone version, supplied with the necessary auxiliary power
As part of a complex system environment, e.g. SIMATIC S7
Description
4.5 System configuration
SITRANS P320/P420 with 4 to 20 mA/HART
38 Operating Instructions, 11/2019, A5E44852162-AC