Level
Setting range: Freely selectable numeric value
Factory setting: 0 m
Volume
Setting range: Freely selectable numeric value
Factory setting: 0 m
3
Volume flow
Setting range: Freely selectable numeric value
Factory setting: 0 m
3
/s
Setting range: Freely selectable numeric value
Factory setting: 0
Mass flow
Setting range: Freely selectable numeric value
Factory setting: 0 kg/s
Setting range: Freely selectable numeric value
Factory setting: 0
Custom units
Setting range: Freely selectable numeric value
Factory setting: USER DEFINED (custom), or as specified in order
Note
Bidirectional volume and mass flow measurement
Select a lower scaling value that is symmetrical to the upper scaling value. Example:
Upper scaling value: 1000 m
3
/s
Lower scaling value: -1000 m
3
/s
9.2.16.1 Set lower scaling point
1. Navigate to the parameter view.
Navigating in the views
(Page 76)
2. Select the "Lower scaling point" parameter [18].
3. Use the
button to confirm.
4. Set the lower scaling point.
Parameter assignment
9.2 Parameter assignment over device with display
SITRANS P320/P420 with 4 to 20 mA/HART
Operating Instructions, 11/2019, A5E44852162-AC 131