Procedure
1. Mount the device.
Installing
(Page 47)
Installation (level) (Page 51)
2. Connect the device.
Connecting the device (Page 68)
3. Switch on the supply voltage.
Switching on the supply voltage (Page 88)
4. Open the cover of the buttons:
Figure 8-2 Top view
5. Set the measuring range.
Set lower range value/upper range value (without pressure available) (Page 109
)
Apply lower range value/upper range value (with pressure present) (Page 122)
6. Set the pressure unit.
Pressure units [01] (Page 106)
7. Set the application of your device.
Application [05] (Page 110)
8. Set the scaling points.
Lower scaling point [18] (Page 130)
Upper scaling point [19] (Page 132)
9. Set the zero point.
Adjusting zero point (gauge pressure) (Page 120)
Adjusting the zero point (differential pressure) (Page 121)
Adjusting zero point (absolute pressure) (Page 121)
10.Lock the device.
Locking the device (Page 82)
11.Enable Functional Safety (for devices with Functional Safety).
Enabling Functional Safety over device with display (Page 167)
You can find additional functions in the section Parameter assignment (Page 101)
Commissioning
8.4 Commissioning the device with display
SITRANS P320/P420 with 4 to 20 mA/HART
Operating Instructions, 11/2019, A5E44852162-AC 91