Procedure
$
%
A Pressure transmitter above the differential
pressure transducer
B Pressure transmitter below the differential
pressure transducer
① Pressure transmitter ⑦ Blowout valves
② Stabilizing valve ⑧ Condensate vessels (optional)
③,
④
Differential pressure valves ⑨ Differential pressure transducer (e.g.
FPS200 and FPS300)
⑤ Differential pressure lines ⑩ 3-way valve manifold
⑥ Shut-off valves
1. Open both the shut-off valves ⑥ at the pressure tapping point.
2.
Open the stabilizing valve ②
.
3. Open the differential pressure valve (③ or ④).
4. Check and, if necessary, correct the zero point when the lower range value is 0 bar (4 mA).
5. Close the stabilizing valve ②.
6. Open the other differential pressure valve (③ or ④).
Commissioning
8.5 Application examples
SITRANS P320/P420 with 4 to 20 mA/HART
Operating Instructions, 11/2019, A5E44852162-AC 95