Procedure


$
%
A Pressure transmitter below the differential pres‐
sure transducer
B Pressure transmitter above the differential pres‐
sure transducer
Pressure transmitter Drain valves
Stabilizing valve Gas collector vessels (optional)
, Differential pressure valves Differential pressure transducer
Differential pressure lines Vent valves
Shut-off valves 5-way valve manifold
1. Open both the shut-off valves at the pressure tapping point.
2.
Open the stabilizing valve
.
3. With pressure transmitters below the differential pressure transducer, partially open both
drain valves one after the other until liquid emerges without bubbles.
In the case of a pressure transmitter above the differential pressure transducer, partially
open both vent valves one after the other until liquid emerges without bubbles.
4. Close both drain valves or vent valves .
5. Partially open the differential pressure valve and the vent valve (sealing plug with vent
valve) on the positive side of the pressure transmitter until liquid escapes without bubbles.
6. Close the vent valve (sealing plug with vent valve).
7. Partially open the vent valve (sealing plug with vent valve) on the negative side of the
pressure transmitter until liquid escapes without bubbles.
8. Close the differential pressure valve .
Commissioning
8.5 Application examples
SITRANS P320/P420 with 4 to 20 mA/HART
Operating Instructions, 11/2019, A5E44852162-AC 97