SW1 -3 through SW1 -6 = Power Supply configuration
DIP Switch Position
3 4 5 6
1 0 0 1
1 0 1 0
Configuration Interpretation
Power Supply w/lead-acid battery
Power Supply w/o batter charger
I1101
1 Power Supply w/Audio (25W Amp) & lead-acid battery
I
I~------
1 1 1 0
I
Power Supply w/Audio (25W Amp) w/o battery charger
I
1 0 0 0 Power Supply w/NICAD battery
1 1 0 0 Power Supply w/Audio (25W Amp)
& NICAD battery
SW1 -7 = Position 0, enables 50 Ah battery charging.
Position 1, enables 110 Ah battery charging.
SW1 -8 = Spare
SW2-1 ON = 9600 baud.
SW2-1 OFF = 1200 baud.
Sw2-2 through SW2-8 determine the board address.
Jumpers
JWl-7 = PROM Configuration Jumpers. The PROM Configuration Jumpers are factory-installed and will change
only if the PROM type is changed. These jumpers are not field-selectable. Please refer to publication FA4-
21-234 for more information on jumper settings when PROM types are changed.
P6
Jumper Pins l-2 for Normal Configuration.
Jumper Pins 2-3 for No Battery Configuration.
P7, PlO & P13 are factory-adjusted. These circuits are not field adjustable.
P16
Jumper Pins l-2 to enable Earth Detect.
Jumper Pins 2-3 to disable Earth Detect.
Connectors
Refer to Field Wiring Diagrams 841-843 and 841-845 for harness interconnections. Refer to Publication FA4-21-234
for additional information.
Power Harness =
RED wire to the + connection on the switcher board
BLACK wire to the - connection on the switcher board
Yellow wire to the CHG connection on the switcher board
Pl = A Tap Signal Supervisory Input
P2 = B Tap Signal Supervisory Input
P3 = C Tap Signal Supervisory Input
P4 = 4100 Communications Interface for use by the communicating supply