I
NOTE 1:
Terminate field wiring in accordance with the appropriate 4100 Field Wiring Diagram (841-731).
NOTE
2:
A feedback point monitors the controlled device.
UT MASTER MOTHERBOARDS
BOARD IDENTIFICATION
Two types of 41 OO+/UT Master Motherboards are available, each can be identified by the name and number it bears.
UT Master Motherboard (565-l 61)
l
This card is the backplane for the 4100+/UT Master Controller and an optional communications card. No city
connect is provided.
UT Master Motherboard (565-213)
l
This card is the backplane for the 4100+/UT Master Controller and an optional communications card. A city
connect is also provided.
COMPONENT LOCATIONS AND FUNCTIONS
(FIGURE 7 & 8)
Connectors (565161)
PI ,Jl
Both power and comm are passed to adjacent motherboards via Pl and Jl .
P2
l
Internal communications can be connected via P2
P3
l
System power is connected to the board via P3.
J2
l
The 2120 Comm/RS232 card plugs into J2.
J3
l
The UT Master Controller card plugs into J3.
Terminal Blocks (565 161)
Field connections for the Master Controller and the Comm Card are made at the motherboard terminal blocks TBl
and TB2. Internal Power and Communications connections are listed below.
TXD (Serial Communications Transmit)
PI -1, P2-1, P2-5, JI-1, J2-10, J3-10
COMMON (Serial Communications Common)
Pl-2, P2-2, P2-6, Jl-2, J2-L, J3-L
RCV (Serial communications receive) Pl-3, P2-3, P2-7, Jl-3, J2-11, J3-11
CODE (coded signal bus line) Pl-4, P2-4, P2-8, Jl-4, J2-M, J3-M
8C (8-volt common, OV)
PI-5, Pl-6, P3-5, JI-5, Jl-6, J2-12, J3-12
+8V (+8-volt system power) Pl-7, P3-2, P3-6, Jl-7, J2-N, J3-N
24C (24-volt common, OV) PI-8, Pl-9, P3-3, P3-7, Jl-8, Jl-9, J2-13, J3-13
+24V (+24-volt system power)
PI-IO, P3-4, P3-8, Jl-10, J2-P, J3-P
11
firealarmresources.com

Table of Contents

Other manuals for Simplex 4100+

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Simplex 4100+ and is the answer not in the manual?

Simplex 4100+ Specifications

General IconGeneral
TypeAddressable Fire Alarm Control Panel
SLC LoopsUp to 10
Operating Temperature32°F to 120°F (0°C to 49°C)
Humidity Range10% to 93% non-condensing
DisplayLCD
CommunicationEthernet
Power Supply120/240 VAC, 50/60 Hz
Battery Backup24 VDC
NAC OutputsExpandable
Releasing CapabilityYes, with releasing modules
Max Notification Appliance Circuits (NACs)Varies by modules
Max Releasing Circuits10
Communication PortsEthernet
Max Devices3, 000

Related product manuals