AUDIO CONTROLLER BOARD
(562-894l(FIGURE 48)
If required, adjust the following potentiometers to obtain a reading of 500 mV RMS unless stated otherwise (turning
potentiometers clockwise increases outputs).
l
R46 = Channel 1. Measure between P9-1 and P9-2.
l
R93 = Channel 2. Measure between P8-1 and P8-2.
l
R96 = Channel 3. Measure between P7-1 and P7-2.
l
R80 = Phone Paging. Adjust to desired sound level. Not to exceed 350 mv RMS when measured between TP5
and TBl-3 while using telephone.
l
R105 = Local Speaker. Adjust to desired sound level. R88 = Network Audio. Adjust to 350 mv RMS when a signal
is present at TB2 (measure between TP6 and TBl-3).
R105
R46 R96 R93
TBl R80
R88
\
\
-. -
nr
a.
,
3 m
Y
/
P6
\I = I
q,sdY NO.
TP5
P7
T@6 TB2
Figure 48
Audio Controller Board Component Locations
82
firealarmresources.com

Table of Contents

Other manuals for Simplex 4100+

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Simplex 4100+ and is the answer not in the manual?

Simplex 4100+ Specifications

General IconGeneral
TypeAddressable Fire Alarm Control Panel
SLC LoopsUp to 10
Operating Temperature32°F to 120°F (0°C to 49°C)
Humidity Range10% to 93% non-condensing
DisplayLCD
CommunicationEthernet
Power Supply120/240 VAC, 50/60 Hz
Battery Backup24 VDC
NAC OutputsExpandable
Releasing CapabilityYes, with releasing modules
Max Notification Appliance Circuits (NACs)Varies by modules
Max Releasing Circuits10
Communication PortsEthernet
Max Devices3, 000

Related product manuals