Error no. Explanation Inverter behavior Corrective measures
S1 S2 R
3601 Leakage current to ground has oc-
curred in the PV array or the
threshold defined in parameter
RisoCtlWarn has been reached.
W W ‒ • Check the grounding and equipotential
bonding.
• Check the module wiring and system
design.
• Check the parameter RisoCtlWarn.
3803 The PV array current is too high. 1 min D ‒ • Check the DC input current.
• Check the module wiring and system
design.
4003 Reverse currents detected in the PV
array or DC connection polarity
reversed.
30s Q ‒ • Check the PV modules for short circuits.
• Check the module wiring and system
design.
• Check the DC terminals for correct
polarity.
• Check the functionality of the entire
string.
Error no. Explanation Inverter behavior Corrective measures
S1 S2 R
3403 PV array voltage is too high. 15
min
30
min
‒ • Check the DC voltage.
• Check the module wiring and system
design.
3404 Open-circuit voltage is too high.
Disturbance detected by standard
monitoring.
15
min
30
min
‒
3406 The DC voltage is too high. 15
min
30
min
‒
3501 The insulation monitoring device
has measured a too low ground-
ing resistance.
C C ‒ • Check the PV array for ground faults.
3502 The GFDI has tripped. C C ‒ • Check the PV array for ground faults.
3504 The insulation monitoring device
has detected an insulation error.
If the parameter IsoErrIgn is set to
On, this error is ignored.
W W ‒ • Check the PV array for ground faults.
3507 A ground fault has occurred on
the ungrounded terminal of the PV
array.
Q Q ‒ • Check the PV array for ground faults.
3510 The inverter has detected an insu-
lation error on the inverter bridge.
Q Q ‒ • Check the PV array for ground faults.
3511 The inverter has detected an insu-
lation error.
W W ‒ • Check the PV array for ground faults.