Damage to eyes and skin due to visible and invisible laser radiation
The product contains class1 LED or laser components in accordance with IEC60825-1(2003). The laser beam
appears at the end of the optical fiber. Incorrect handling with laser beams can result in damage to eyes and skin.
Do not look into the laser beam.
Do not look at the laser beam using optical instruments.
Do not point the laser beam at persons.
Procedure:
1. Insert the optical fibers into the patch panel from below and
splice using optical fiber pigtails (see the patch panel
documentation). Observe the maximum permissible tension
and the minimum permissible bend radii of the optical fibers.
2. Connect the patch panel to the network switch using the optical fiber patch cables included in the delivery (bend
radius: 100mm). Observe the send and receive directions of the optical fiber nodes.
5.7.1.2 Connecting the Network Cables
Network cable requirements:
The network cables must be shielded and pair-twisted.
The network cables must be of at least category5 (CAT5).
Maximum cable length: 100m
Requirement:
The network cables must be correctly inserted through the base plates of the MVPowerStation and in the
Communit (see Section12.4, page167).
Procedure:
Connect the network cables to the network terminals in accordance with the circuit diagram.
5 Installation
SMA Solar Technology AG
System ManualMVPS22JP-SH-en-1164