Loading...
Name Description Value/range Explanation Default
value
ExlTrfErrEna Activation of hermetic
protection of MV trans-
former
Off Deactivated On
On Activated
* To view or change this parameter, you must enter the installer password.
** To change this parameter, you must enter the installer password.
*** You can only view this parameter.
14.2.2 SunnyCentralString-MonitorController
Name Description Value/range Explanation Default
value
Serial Number Display of serial number The value cannot be changed.
Firmware Firmware version of operation
control unit
0 to 255
Firmware2 Firmware version of digital signal
processor
0 to 255
Dt Entry of current date 20060101 to
20991231
Entered in the format
YYYYMMDD
Tm Entry of current time 0 to 235959 Entered in the format
HHMMSS
TolGr1* Deviation of group1 currents
from mean value
5% to 100% Parameter exists for all six
groups.
13%
MoniTmGr1On
*
Start time for monitoring of
group1
07:00 a.m. to
7:00 p.m.
Parameter exists for all six
groups.
10:00 a.m.
MoniTmGr1Off
*
End time for monitoring of
group1
07:00 a.m. to
7:00 p.m.
Parameter exists for all six
groups.
3:00 p.m.
MoniTmGrAl-
lOn*
Start time for monitoring of all
groups
07:00 a.m. to
7:00 p.m.
10:00 a.m.
MoniTmGrAl-
lOff*
End time for monitoring of all
groups
07:00 a.m. to
7:00 p.m.
3:00 p.m.
MoniTmComO
n*
Start time for monitoring of all
groups
07:00 a.m. to
7:00 p.m.
10:00 a.m.
MoniTmComOf
f*
End time for monitoring of all
groups
07:00 a.m. to
7:00 p.m.
3:00 p.m.
Ackn Acknowledge errors quit
14 Operating Data and Parameters