5.6 Installing the DC Connection
5.6.1 Connecting the DC Cable to the Busbar
Figure 32: Dimensions of the DC busbar (example)
Position Designation
A Connection area DC+
B Connection area DC‒
C DC connection bracket with dimensions
Terminal lug requirements:
Use tin-plated terminal lugs only.
For the connection, only the supplied screws, washers and nuts must be used.
The terminal lugs must be designed according to the temperature. Temperature: +95°C
The width of the terminal lugs must exceed the washer diameter. Washer diameter: 32mm. This will ensure that
the defined torques are effective over the whole surface.
Cable requirements:
The DC cables must be designed for the maximum PV voltage and must have double or reinforced insulation.
No more than two cables must be connected to each DC terminal.
Use copper or aluminum cables only.
Maximum cable cross-section:400mm².
Terminal lugs: M12
5 Installation
SMA Solar Technology AG
System ManualMVPS22JP-SH-en-1160