Danger to life due to applied voltages as a result of automatic reconnection
If the automatic cascade control is activated, it is possible that the voltage is automatically reconnected when
working on the medium-voltage switchgear. Touching live components can result in death or serious injury due to
electric shock.
For the order option "Cascade control", deactivate the automatic reconnection function at the control device
and the medium-voltage switchgear.
Deactivate the automatic reconnection function in the superordinate MVPowerStation with cascade control.
Ensure that the control device cannot be accidentally switched on again.
Wear suitable personal protective equipment for all work on the product.
Hearing impairment due to high-frequency noises of the inverter
The inverter generates high-frequency noises when in operation. This can result in hearing impairment.
Wear personal protective equipment for all work on the product.
Wear hearing protection.
Risk of burns due to hot components
Some components of the product can get very hot during operation. Touching these components can cause burns.
Observe the warnings on all components.
During operation, do not touch any components marked with such warnings.
After switching off the product, wait until any hot components have cooled down sufficiently.
Wear suitable personal protective equipment for all work on the product.
Connect and disconnect the AC voltage of the MV transformer
Only a duly authorized person is allowed to connect and disconnect the AC voltage of the MV transformer.
7 Disconnecting and Reconnecting
SMA Solar Technology AG
System Manual 97MVPS22JP-SH-en-11