ALC404 LIGHTING TOWER CONTROLLER USER MANUAL
ALC404 Lighting Tower Controller 2018-11-06 Version 1.1 Page 37 of 83
Enable Fast Loading Feature
0 Disabled 1 Enabled
After fast loading enabled,
engine starts and enters
into stage of safety on
delay, and if genset meet
the requirements of loading
condition, it will directly
enter into ready for load
stage.
It is the maximum start
attempts if genset fail to
start. If the preset start
attempts been reached,
controller will send start fail
signal.
AC genset reference to
Table 25 AC GENSET
CRANK DISCONNECT
CONDITION; DC genset
reference to Table 26 DC
GENSET CRANK
DISCONNECT
CONDITION.
There are 3 conditions to
make starter disconnected
with engine, and they all
can be used separately or
simultaneously aiming to
disconnect starter motor
with engine as soon as
possible.
The setting value is rated
frequency pct. of genset.
When genset frequency is
above the setting limit,
starter will disconnect.
Details to see the following
installation instructions.
The setting value is rated
speed pct. of genset. When
genset speed is above the
setting limit, starter will