ALC404 LIGHTING TOWER CONTROLLER USER MANUAL
ALC404 Lighting Tower Controller 2018-11-06 Version 1.1 Page 38 of 83
disconnect. Details to see
the following installation
instructions.
When genset oil pressure is
above the setting limit,
starter will disconnect.
Details to see the following
installation instructions.
The setting value is rated
voltage pct. of DC genset.
When DC power voltage is
above the setting limit,
starter will disconnect.
Details to see the following
installation instructions.
Rated Starting Battery Voltage
Provide standard for
judging battery over/under
voltage and charge fail.
Battery Charge
Alternator Failure
Warning
The setting value is
percentage of starting
battery rated voltage. While
genset in normal running
stage, if D+(WL) voltage of
charger bellows setting limit
and delay time is expired,
controller will send charge
fail warning signal.
The return value is
percentage of starting
battery rated voltage. If
controller has sent charge
fail warning signal, when
D+(WL) voltage exceeds
return value, charge fail
warning will reset
automatically.
Battery Under
Voltage Warning
The setting value is
percentage of starting
battery rated voltage