ALC404 LIGHTING TOWER CONTROLLER USER MANUAL
ALC404 Lighting Tower Controller 2018-11-06 Version 1.1 Page 41 of 83
Category
Parameters
Range
Default
Description
Note: this function is only active in safety running period. This moment, over
speed shutdown delay is overshoot delay, and calculation formula of speed
limit is speed limit=rated speed * over speed % * (1+overshoot %).
Fuel Pump Control
Enable
(0~1)
0
0 Disabled 1 Enabled
Turn On
(0~1000)%
10
If fuel level bellows turn on
limit, output port of fuel
pump control starts output.
Turn Off
(0~1000)%
80
If fuel level exceeds turn off
limit, output port of fuel
pump control stops output.
Max.
Time(Turn
On)
(0~3600)s
60
It is the maximum output
time of fuel pump control,
aiming to prevent fuel pump
continues working because
of the sensor fault.
Fuel Tank Capacity
Enable
(0~1)
0
0 Disabled 1 Enabled
Capacity
(0~10000)L
100
After it is enabled, liquid unit
displayed on the mains
screen is changed from %
to L. conversion formula:
Fuel capacity = tank
capacity * fuel level
Coolant Temperature Associated
(0~3)
1
0 Not Associated
1 ALC404 Sensor 1
2 ALC404 Sensor 2
3 ALC404 Sensor 3
Note: if select engine with
ECU, this parameter is
invalid, and coolant temp.
and oil pressure data
displayed on controller main
screen are transferred by
ECU.
Oil Pressure Associated
(0~3)
2
Fuel Level Associated
(0~3)
3
0 Not associated
1 ALC404 Sensor 1
2 ALC404 Sensor 2
3 ALC404 Sensor 3
Generator
Generator Type
(0~4)
0
0 3Phase, 4Wire(3P4W)
1 3Phase, 3Wire(3P3W)
2 1Phase, 2Wire(1P2W)
3 2Phase, 3Wire(2P3W)
4 DC Power
Enabled
(0~1)
0
0 Disabled 1 Enabled