ALC404 LIGHTING TOWER CONTROLLER USER MANUAL
ALC404 Lighting Tower Controller 2018-11-06 Version 1.1 Page 47 of 83
Category
Parameters
Range
Default
Description
max. number of turned on
lights that allowed to
number of lights that
allowed in this mode.
Recover
Light-on
Amount
Level
(0~1000)%
25
While genset is normal
running, when fuel level
exceeds the setting limit
after controller sent fuel
level drop turn off the light
warning signal, the number
of turned on lights allowed
return to the pre-set total
lights.
Delay
(0~3600)s
30
It is delay time to confirm
that fuel level drop turn off
the light warning.
Allowed
Light-on
Amount
(0~4)
1
The number of turned on
lights that allowed after
controller sending fuel level
drop turn off the light signal.
Note: This function is invalid when mains power supply is active or fuel
level does not associate with sensors.
Sensors
Flexible Sensor 1
Details please to see7.3
FLEXIBLE SENSOR 1
SETTINGS
Flexible Sensor 2
Details please to see7.4
FLEXIBLE SENSOR 2
SETTINGS
Flexible Sensor 3
Details please to see7.5
FLEXIBLE SENSOR 3
SETTINGS
ECU Coolant
Temperature
High
Shutdown
Enable
(0~1)
1
0 Disabled 1 Enabled
Set
Value
(0~300)
98
Delay
(0~3600)s
3
High
Warning
Enable
(0~1)
1
0 Disabled 1 Enabled
Set
Value
(0~300)
95
Return
Value
(0~300)
93
Delay
(0~3600)s
5
ECU Oil
Pressure
Low
Shutdown
Enable
(0~1)
1
0 Disabled 1 Enabled
Set
Value
(0~1000)kPa
103