Those alarms OID and description are reported in TRAP 3 (added) and TRAP 4 (removed)
OID .1.3.6.1.2.1.33.1.6.3 JBUSP VU-MAP
.1 upsAlarmBatteryBad A01 or A47 A027 or A20 or A21
.2 upsAlarmOnBattery S05 A019
.3 upsAlarmLowBattery S15 A018
.4 upsAlarmDepletedBattery S16|A49 A017
.5 upsAlarmTempBad A07 A002
.6 upsAlarmInputBad A05 A035
.7 upsAlarmOutputBad Not available
.8 upsAlarmOutputOverload A02 A001
.9 upsAlarmOnBypass S04&!S07 S002&!S006
.10 upsAlarmBypassBad A29 A049 Critical alarm
.11 upsAlarmOutputOffAsRequested Not available
.12 upsAlarmUpsOffAsRequested Not available
.13 upsAlarmChargerFailed A26 A038
.14 upsAlarmUpsOutputOff !S03&!S04 S004
.15 upsAlarmUpsSystemOff !S02 & !S03 & !S04 !S049 & !S52 & !S57
.16 upsAlarmFanFailure A60 A054
.17 upsAlarmFuseFailure Not available
.18 upsAlarmGeneralFault A00 A015
.19 upsAlarmDiagnosticTestFailed S14 A022 Battery test failed
.20 upsAlarmCommunicationsLost NV alarm
.21 upsAlarmAwaitingPower Shutdown agent
.22 upsAlarmShutdownPending Shutdown agent
.23 upsAlarmShutdownImminent Shutdown agent
.24 upsAlarmTestInProgress S10 A034 Battery test